Power rating | 300 W |
---|
Item | Output voltage | 12 V | 15 V | 24 V | 48 V |
---|
Efficiency | 100 VAC input | 81% typ. | 81% typ. | 82% typ. | 82% typ. |
200 VAC input | 85% typ. | 85% typ. | 87% typ. | 87% typ. |
230 VAC input | 85% typ. | 86% typ. | 87% typ. | 87% typ. |
Input | Voltage range | Single phase, 85 to 264 VAC, 120 to 370 VDC |
Frequency | 50/60 Hz (47 to 63 Hz) |
Current | 100 VAC input | 4.2 A typ. |
200 VAC input | 2.1 A typ. |
Power factor | 0.9 min. |
Leakage current | 100 VAC input | 0.5 mA max. |
200 VAC input | 1 mA max. |
Inrush current (for a cold start at 25°C) | 100 VAC input | 14 A typ. |
200 VAC input | 28 A typ. |
Output | Rated Output Current | 25 A | 20 A | 14 A | 7 A |
Voltage adjustment range | −10% to 15% (with V.ADJ) |
Ripple & Noise voltage | 100 to 240 VAC input | 140 mVp-p max. | 270 mVp-p max. | 150 mVp-p max. | 330 mVp-p max. |
Input variation influence | 0.5% max. |
Load variation influence | 1.0% max. |
Temperature variation influence | 100 to 240 VAC input | 0.05%/°C max. |
Startup time | 100 VAC input | 1,000 ms max. |
200 VAC input | 1,000 ms max. |
Hold time | 100 VAC input | 30 ms typ. | 30 ms typ. | 30 ms typ. | 30 ms typ. |
200 VAC input | 30 ms typ. | 25 ms typ. | 30 ms typ. | 30 ms typ. |
Additional functions | Overload protection | Yes, automatic reset |
Overvoltage protection | Yes, 120% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again) |
Overheat protection | Yes, power shut off (shut off the input voltage and turn on the input again) |
Series operation | Yes (For up to two Power Supplies, external diodes are required.) |
Parallel operation | No (However, backup operation is possible, external diodes are required.) |
Remote sensing | No |
Remote control | Yes (Only for models with remote control option) |
Output indicator | Yes (LED: Green) |
Insulation | Withstand voltage | 3 kVAC for 1 min. (between all input terminals and output terminals) current cutoff 20 mA |
2 kVAC for 1 min. (between all input terminals and PE terminals) current cutoff 20 mA |
1 kVAC for 1 min. (between all output terminals and PE terminals) current cutoff 20 mA |
Only Remote control 500 VAC for 1 min. (between all output terminals and RC terminals) current cutoff 20 mA |
Insulation resistance | 100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC |
Environment | Ambient operating temperature | −20 to 70°C (with no condensation or icing) |
Storage temperature | −25 to 75°C (with no condensation or icing) |
Ambient operating humidity | 90% max. (Storage humidity: 90% max.) |
Vibration resistance | 10 to 55 Hz, 4.5 G max., 0.375-mm half amplitude for 2 h each in X, Y, and Z directions |
Shock resistance | 150 m/s², 3 times each in ±X, ±Y, ±Z directions |
Reliability | MTBF | 135,000 hrs min. |
Life expectancy | 10 years min. |
Standards | Harmonic current emissions | Conforms to EN 61000-3-2 |
EMI | Conducted Emissions | Conforms to EN 61204-3 Class B, EN 55011 Class B |
Radiated Emissions | Conforms to EN 61204-3 Class B, EN 55011 Class B |
EMS | Conforms to EN 61204-3 high severity levels |
Safety Standards | UL 508 (Listing, excluding models with remote control option) UL 508 (Recognition, models with remote control option) UL 60950-1 (Recognition, OVCII [≤ 3,000 m], Pol2) CSA C22.2 No.107.1 (excluding models with remote control option) CSA C22.2 No.60950-1 (excluding models with remote control option) EN 50178 (OVCIII [≤ 2,000 m], OVCII [> 2,000 m and ≤ 3,000 m], Pol2) EN 60950-1 (OVCII [≤ 3,000 m], Pol2) Conforms to EN/IEC 61558-2-16. |
Marine Standards | No |
SEMI | Conforms to F47-0706 (200 VAC input) |